An emergency flare for hydrogen-rich syngas needs a detonation-rated flame arrester, a burner designed for hydrogen’s fast flame, and careful control of combustion air. For a methanol plant in southern Europe venting about 4,000 Nm³/h of gas that is 58% hydrogen, the proposed design was an enclosed combustor at 1,000°C minimum with 0.3 seconds of residence, plus a separate burner design note for an open hydrogen option.
The challenge: hydrogen behaves differently from landfill gas
The gas in this enquiry was around 58% H₂, 14% CO, 15% N₂, 6% O₂ and a little water, CO₂ and methanol. Its energy content per kilogram is comparable to natural gas, but:
- Hydrogen’s flame speed is about seven times that of methane.
- Its flammable range in air is about 4 to 75%, against about 5 to 15% for methane.
- The 6% oxygen in the gas helps flame stability but means less combustion air is needed.
Autoignition temperatures of about 535°C for hydrogen and 609°C for CO mean both are readily destroyed at 1,000°C. The duty was emergency relief and maintenance venting only: rare, but at full flow when it happens.
The approach: modify a proven enclosed flare
| Feature | Change for hydrogen |
|---|---|
| Flame arrester | Detonation-rated, EN 12874, hydrogen (IIC) group |
| Combustion air | PLC control recalibrated; less air because of oxygen in the gas |
| Burner | 310 stainless steel retained; enclosed shroud and ceramic insulation manage the flame temperature |
| Hazardous area | Zone 1, with ATEX documentation |
| Performance | Destruction of at least 99.5% for CO and hydrogen |
The enclosed flare used a 100 mm ceramic-lined stainless steel shroud, automatic temperature control and double block valve proving. The UK expectation for enclosed flares is 1,000°C and 0.3 seconds, set out in the Environment Agency’s LFTGN05.
Open hydrogen burner: the design note
A supporting design note sized an open, non-premixed multi-port burner for about 9 MW. The principles are useful in their own right:
- No premixing. No venturi or inspirator, so all mixing happens outside the metalwork and flashback inside the burner is avoided.
- Port velocity about 230 m/s through 8 mm drilled ports keeps the jets stable. That needs about 0.5 bar g in the header, so the pressure drop across the ports is more than ten times the pressure drop along the bars, giving even flow.
- 96 ports on six bars (20, 16 and 12 per bar, scaled to bar length), fed symmetrically from a large header.
- Shroud for wind shielding only, open at the top, with drain holes and freeboard above the bars.
- Two or three pilots and UV or multi-spectrum flame detection, since a hydrogen flame is nearly invisible. Pilot gas should be natural gas or propane, not hydrogen.
- No carbon steel in the flame zone; 310S stainless for the hot parts.
- Nitrogen purge of the manifold when idle, and no dead legs that trap air.
Screening noise estimate
Ninety-six jets at 230 m/s were estimated at roughly 100 to 105 dB(A) at 1 m above the shroud opening. With free-field spreading, that falls to about 70 to 75 dB(A) at 30 m and 60 to 65 dB(A) at 100 m. The note describes this as a screening estimate, not a replacement for an acoustic model, and an emergency-only duty makes it more acceptable. A detailed assessment was left to detailed design.
What to consider for your own project
- Get the gas composition and relief cases, not just a flow.
- Specify the arrester for the gas group.
- Treat flame detection as critical.
- Check noise and radiation early for emergency duty.
- Agree the hazardous area classification using DSEAR principles in the UK.
For a conventional landfill gas example, see ground flare versus elevated flare.
FAQ
Can a landfill gas flare burn hydrogen?
Not without modification. The arrester, air control and detection all need upgrading.
Why is hydrogen flame detection hard?
The flame is nearly invisible, so UV or multi-spectrum detection is used.
Why use a high port velocity?
It prevents flashback and keeps jets stable.
Is the noise a problem?
For emergency-only use, the screening estimate suggests typical boundary limits can be met, subject to detailed assessment.
Venting hydrogen-rich gas?
Tell us your gas composition and relief cases and we will discuss a design.