A bioscrubber removes hydrogen sulphide (H₂S) from biogas using bacteria growing on a packed bed. It needs no routine chemical dosing and is cheaper to build and run than most alternatives. This article describes a 600 Nm³/h unit quoted for a farm biogas project in South-East Asia, designed to bring H₂S from up to 2,000 ppm down to 250 ppm.
The challenge: sulphide in the gas
H₂S forms from proteins and sulphates during anaerobic digestion. Concentrations range from a few ppm, where iron salts are present, up to about 4% by volume with some wastes. It is removed to meet environmental limits and to prevent corrosion, particularly where gas runs engines or boilers.
The alternatives include sodium hydroxide wet scrubbers, dry iron-based scrubbers, adding iron salts to the digester, chelated iron solutions, dry-bed adsorption and bacteria. Most of those have a high investment cost or high operating cost from chemicals and waste disposal. The biological approach is highly efficient and cheaper to build and run.
The design basis
| Parameter | Value |
|---|---|
| Biogas flow | 120 to 600 Nm³/h |
| H₂S in | up to 2,000 ppm |
| H₂S out | 250 ppm |
| Methane | 60 to 70% |
| Gas temperature | up to 45°C, saturated |
| Vessel | One, 3.0 m diameter by 7 m high, glass-reinforced plastic |
| Rate of change | Flow and H₂S each assumed to vary by no more than 1% a minute |
How it works
- Gas enters at the base and rises through a packed bed in a sealed vessel.
- Bacteria on the packing, active at low pH, consume H₂S.
- A variable-frequency blower adds atmospheric air to supply oxygen.
- A recirculation pump, selected for acid duty, sprays liquid over the bed.
- Excess bacteria are removed through a timed auto-drain, set at commissioning, and fresh make-up water keeps the pH from falling too far. Make-up should carry a carbon source, such as lagoon effluent, and be free of excess suspended solids.
Spent liquid is described as safe to send to a normal wastewater drain.
Safety
Biogas and air mixtures can be explosive, so equipment in the gas and air line is protected to Zone 2 or powered intrinsically safely. Pressure and vacuum relief valves protect the plastic vessel.
Instruments and controls
- Oxygen and H₂S cells on the exit gas.
- A pressure switch on the feed line for flow interruption.
- Pressure gauges to monitor bed pressure drop.
- Level switches on the vessels.
- An IP56 PLC panel with start/stop, emergency stop and alarm lamps.
- Inlet gas analysers are offered with a dedicated analyser panel.
Where lower H₂S is needed, a polishing stage such as duty-follow iron sponge vessels can follow, or the scrubber can be enlarged. A heated base tank and insulation help in cold climates.
What to consider for your own project
- Measure the worst-case H₂S. Peaks drive the design.
- Find a carbon source for the make-up liquid.
- Check the downstream limit. Engine manufacturers specify H₂S limits.
- Plan for climate. Cold sites need insulation and heating.
For UK context see the Anaerobic Digestion Strategy and Action Plan.
FAQ
Does a bioscrubber need chemicals?
No routine chemical addition, according to the design; nutrients come from the make-up water.
Why add air to a biogas scrubber?
The bacteria need oxygen to oxidise H₂S.
Can it reach very low H₂S?