A good landfill gas flare specification names its safety devices and monitoring points, not just its flow and temperature. A 1,000 Nm³/h enclosed flare quoted for an Australian contractor makes a useful checklist: double block-and-bleed valves, flame arresters, UV flame detection, a datalogger and an IP66 control panel in a rain shelter.
The challenge: flares fail at the edges
Flares normally run unattended for long periods. The problems that matter happen at start-up, at shut-down and when the gas supply changes. A specification that lists only capacity may leave these cases to chance.
The design basis
- Flow: 200 to 1,000 Nm³/h (5:1 turndown), with thermal output from 1,000 to 5,000 kW.
- Gas: 25 to 70% methane, design point 50%, up to 5% oxygen, saturated.
- Temperature: from 1,000°C up to 1,200°C above 25% methane. Burns cooler on leaner gas, down to about 20% methane.
- Residence time: at least 0.6 seconds.
- Blower: one centrifugal gas blower, suction around -100 mbar g, delivering about 50 mbar g to the flare.
The safety checklist
Gas shut-off
Two electro-hydraulically actuated butterfly valves sit in series on the main gas line, with a manual bleed valve between them. This is a double block-and-bleed arrangement. Both valves close on loss of power or an alarm, and the bleed allows leakage between them to be checked. Using electro-hydraulic actuation means the site does not need a compressed air supply.
Flame arresters
An ATEX-compliant flame arrester to EN 12874 with a stainless steel element is fitted at the blower outlet and flare inlet, with another on the pilot gas line. They stop a flame travelling back into the gas pipework.
Low-pressure and level protection
A low-pressure switch detects blower failure or a blocked line. A level switch in the knockout pot detects condensate build-up before it reaches the blower.
Flame detection and start-up sequence
Start-up is run by a PLC. It uses electric igniters, a UV flame sensor and a secondary air damper that is set mechanically at commissioning and then handed to PID temperature control. Starting a flare is a sequence, not just a spark, and the timings can be adapted to local requirements. In this quotation the control system also included a burner control system compliant with Australian requirements.
Emergency stop
There is a local emergency stop on the blower skid and one on the control panel.
The monitoring checklist
A touch-screen HMI and datalogger continuously record:
- Gas flow, actual and total.
- Gas vacuum and pressure.
- Gas composition: methane and carbon dioxide by infra-red analyser, oxygen by electrochemical cell.
A modem allows remote access over a landline or SIM card, with the subscription by others. Combustion chamber temperature is displayed, an orifice plate flowmeter measures flow and a pitot insertion point on the inlet line allows independent checks. Four DN125 sampling ports with an access platform and ladder allow stack emission tests. The Environment Agency’s LFTGN05 covers monitoring of enclosed flares in the UK.
Built for the weather
The control panel is rated IP66 and sits inside a walk-in rain shelter on the skid. The flare shroud is lined with 100 mm of ceramic blanket. Structural design covers wind loading, and the ground-level radiation is within acceptable limits.
What to consider for your own project
- List safety devices explicitly. Do not assume each bidder includes the same ones.
- Ask for data you will need for reporting. Regulators often want flow, temperature and composition records.
- Check local burner-control rules. Ask what the local regime requires of burner management.
- Plan stack testing. Include safe access to the sampling ports.
- Agree who commissions and trains. Commissioning and staff training were included, while installation was by others.
See also the Environment Agency’s LFTGN03 for UK expectations on managing landfill gas.
FAQ
What is double block and bleed?
Two shut-off valves in series with a vent between them, so that leakage past the first valve is not passed to the burner.
Why UV flame detection?
It responds immediately to flame loss, unlike a thermocouple, which lags.
Why record gas composition at the flare?
It shows when methane is falling or oxygen is rising, which can point to air ingress in the wellfield.
Writing a flare specification?