Vent Gas Flare for Odour Control: The Butyraldehyde Problem

by | Mar 18, 2026 | Process gas flaring

Vent Gas Flare for Odour Control: The Butyraldehyde Problem

A vent gas flare can destroy a highly odorous gas such as butyraldehyde, but only while the gas stream is rich enough to sustain combustion. When the stream tails off, support fuel or a different odour control step is needed. This post follows a 650 m³/h enclosed flare proposed to a chemical company for tank venting, and shows why the questions asked before quoting were as important as the equipment.

The challenge: a very low odour threshold

Butyraldehyde has an odour threshold of about 0.001 ppm by volume. Any emission must therefore be destroyed to an extremely low level. A well-designed ground flare can do this inside its design range, but tank venting is not steady. Flow rises, peaks and falls away, and the tail-off is where odours escape.

The approach: ask first, then size

The turndown limit

The first response was a set of questions. A standard ground flare has a thermal turndown of 10:1. With a maximum flow of 250 Nm³/h containing 0.9 kg/m³ of butyraldehyde, unassisted combustion can only be guaranteed down to 25 Nm³/h at the same concentration, or 250 Nm³/h at 0.09 kg/m³. Below that, the gas no longer carries enough heat. The supplier asked how the vent profile would run, especially at start and finish.

The options for the tail

  • Assisted combustion: add a fuel gas as the butyraldehyde falls away, automatically.
  • Electro-chemical oxidation: divert low-concentration gas to an odour unit better suited to low organic content.
  • Granular activated carbon polishing: twin columns alternating between polishing and chemical regeneration, judged excessive for the job.

The chosen design

The offer used support gas (LPG). The essential requirement was a flare able to destroy very low butyraldehyde concentrations in nitrogen as well as concentrations up to 0.9 kg/m³, a turndown of about 25:1. It was built on the standard 650 m³/h enclosed flare, 1.6 m in diameter and 7 m high, with a consumption of up to 0.015 kg/s of LPG at the weak end. The quantity needed on site depends on the profile of the transition.

Key design points:

  • Combustion chamber at 1,000°C minimum with at least 0.3 seconds residence time, lined with 100 mm of ceramic blanket.
  • Temperature controlled by an air louvre and PID loop with duty/standby probes.
  • A burner that takes either waste gas or support fuel at the same combustion location. As calorific value falls, support fuel increases.
  • Support fuel added on combustion chamber temperature alone. The system does not try to measure the waste gas flow or calorific value. Temperature is what guarantees the emission criteria are met.
  • Controls ramp up quickly when inert waste gas flow rises and ramp down gradually.
  • An LPG pilot burner, a high-voltage spark, and a self-checking UV flame sensor that responds faster than a thermocouple.

Why it works

Controlling on temperature, not on gas analysis, makes the system robust. Whatever the vent gas is doing, the burner holds the chamber in its working band, and the cost is the fuel used during the tail. A control panel with an operator interface, flame-out options (continue, shut down or vent only) and a flame arrester temperature sensor to detect flashback complete the package.

What to consider for your own project

  1. Draw the vent profile. Know the flow and concentration at the start, peak and end.
  2. Size turndown honestly. A flare that cannot reach the bottom of the profile will not control the odour.
  3. Cost the support fuel. It depends on how long the tail is.
  4. Consider the alternatives for low-concentration gas.
  5. Check dangerous substance duties. See the HSE’s DSEAR guidance.

FAQ

Why does a flare need support fuel?

When the waste gas is too dilute to burn on its own, fuel keeps the chamber hot enough for complete destruction.

What is turndown?

The ratio between the maximum and minimum thermal load a flare can handle, here around 25:1 with support gas.

Why control on temperature?

Temperature is what determines destruction, so it is the most direct control signal.

Venting an odorous gas?

Describe your vent profile and we will advise. Related: a small vapour flare for a storage tank.

Start your enquiry :


Translate »
organics.co.uk
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.