Ground Flare or Elevated Flare? A 2,600 m³/h Worked Example

by | Jun 26, 2026 | Landfill gas

Ground Flare or Elevated Flare? A 2,600 m³/h Worked Example

Choose a high-temperature ground flare when exhaust emissions matter most, and an elevated flare when a lower combustion temperature is acceptable and cost is the priority. In a 2,600 m³/h enquiry from a process engineering contractor, the supplier quoted a ground flare holding at least 1,000°C and offered an elevated alternative at a minimum of 850°C. The temperature difference, and a substantial price reduction, were the trade-off.

The challenge: a specification that did not state a temperature

A contractor was preparing a tender for a waste treatment scheme in Ireland. Its enquiry asked for an ex-works flare rated at 2,600 normalised m³/h but did not specify a combustion temperature. That left the supplier to decide what to quote.

Where a specification is silent, a sensible supplier quotes the more capable option and offers a cheaper alternative. That is what happened here.

The approach: quote the ground flare, offer the alternative

The base offer: SC Range ground flare

The gas had a calorific value of about 15 MJ/m³, and the flare was designed around that:

  • Temperature: at least 1,000°C when calorific value is above 9 MJ/m³, falling as it weakens, down to 7 MJ/m³.
  • Residence time: at least 0.5 seconds.
  • Feed pressure: at least 10 mbar at the flare inlet. No booster was part of this supply, so the gas has to arrive at the flare under its own pressure.
  • Shroud: 9 m high, hot-dip galvanised steel lined with 100 mm of ceramic insulation.
  • Control: a PID controller with combustion air louvres and an actuator, plus a thermocouple to detect the flame and electric ignition run by a PLC.
  • Safety: a flame arrester on the inlet, a pressure switch to detect flow interruption and a single-block slam-shut valve.

The operator can choose between continuing to run on flame-out, shutting down on flame-out, or venting only.

The alternative: AC Range elevated flare

An AC Range elevated flare was offered as a lower-specification option. It would meet every other aspect of the specification, with a minimum combustion temperature of 850°C. The supplier quantified the saving in the quotation, which was a substantial reduction on the ground flare price.

Why the choice matters

Ground flare (SC Range)Elevated flare (AC Range)
Minimum combustion temperature1,000°C850°C
Combustion air controlAutomatic, tightMore limited
Flame visibilityHidden in the shroudVisible at the stack tip
Destruction of trace gasesMaximisedLower
Typical useWhere emission control is of senior importanceRemote sites or lighter requirements

Higher temperature gives a higher destruction and removal efficiency for toxic trace gases. In the UK, regulators expect enclosed flares to reach at least 1,000°C with 0.3 seconds of residence time, according to the Environment Agency’s guidance on monitoring enclosed flares (LFTGN05). If your project is in the UK and subject to a permit, the 850°C option is unlikely to be enough on its own.

What to consider for your own project

  1. State a temperature in the enquiry. It avoids pricing the wrong option and saves a revision cycle.
  2. Know your gas calorific value. The flare’s lower operating limit depends on it. This one was designed to run down to 7 MJ/m³.
  3. Check inlet pressure. Without a booster, the gas must reach the flare at the pressure it needs. Here that was at least 10 mbar.
  4. Ask for the alternative. A lower-spec price helps the client judge what the extra performance costs.
  5. Check the regulator’s view first. A cheaper flare that fails a permit is not a saving.

FAQ

What is the difference between a ground flare and an elevated flare?

A ground flare burns gas inside an enclosed shroud with controlled combustion air. An elevated flare burns it at the top of a stack, usually at a lower temperature.

Why does combustion temperature matter?

Higher temperatures destroy toxic trace gases more completely, which is why enclosed flares are specified where emission control is important.

Can a flare run without a booster?

Yes, if the gas arrives at the flare inlet at enough pressure. This design needed a minimum of 10 mbar.

What happens when the flame goes out?

The operator selects the response in advance: keep running, shut down, or vent only.

Choosing a flare type?

Tell us about your gas and your permit and we will recommend a flare type.

Start your enquiry :


Translate »
organics.co.uk

Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.