Flaring Low-Methane Landfill Gas: A 350 Nm³/h Flare and Blower Package

by | Feb 25, 2026 | Landfill gas

Flaring Low-Methane Landfill Gas: A 350 Nm³/h Flare and Blower Package

Landfill gas with as little as 12% methane can still be flared safely if the flare is designed for it. The key features are a lower combustion temperature set point, automatic temperature control, a propane pilot for starting and a blower that holds a steady suction. This post walks through a skid-mounted package rated at 350 Nm³/h for an Australian landfill, with a 400 Nm³/h blower.

The challenge: gas quality that changes over time

As a landfill ages, gas production falls and the methane fraction drops, often because air is drawn into the gas field. A flare designed only for 50% methane gas can fail to hold a flame when the gas weakens. The specification here covered 12% to 60% methane, with 0 to 5% oxygen.

The flow changes with the calorific value. As the gas gets richer, the volume handled falls. The flare therefore works over a thermal range of about 5:1, with a minimum flow of 70 Nm³/h.

The approach: one skid, blower and flare together

The blower

  • One stainless steel centrifugal blower, 400 Nm³/h, up to 250 mbar head, with a hazardous-area (ExN) motor.
  • A variable speed drive, which can hold a fixed speed or control the vacuum at the blower inlet automatically.
  • A knockout pot with a polypropylene demister (about 99% removal of particles above 6 microns), a pressure gauge across the filter and a drain.
  • Block-and-bleed inlet valves, a strainer, flexible joints and a low-pressure switch to detect blockage or blower failure.

The flare

  • An enclosed ground flare with a ceramic-blanket-lined shroud (100 mm), lined to keep heat in and skin temperature safe.
  • A combustion temperature from 750°C up to 1,100°C. At methane above 12% the controller holds at least 750°C.
  • A residence time of at least 0.3 seconds and four sampling ports for emissions testing.
  • A PID controller driving an air louvre from thermocouple readings.
  • Electric ignition under PLC control, with a UV flame sensor, a purge blower and a fail-safe slam-shut valve that closes on power loss or alarm.
  • A propane pilot, because a landfill gas pilot may not light reliably on very lean gas.

Why a lower temperature is acceptable here

Lean gas contains little energy. Holding 1,000°C would need a lot of air control and may not be achievable, so a lower floor of 750°C applies once methane drops. This has to be agreed with the regulator in the project’s jurisdiction. In the UK, the Environment Agency’s guidance expects enclosed flares to meet at least 1,000°C and 0.3 seconds, as set out in LFTGN05. Check which standard applies before specifying a lower figure.

Control, alarms and remote access

  • A datalogger records flare temperature, gas pressure and temperature, flow, and methane and oxygen at 15-minute intervals.
  • A GSM modem sends alarms by SMS and email and allows remote start and stop.
  • Alarms cover high and low flare temperature, low pressure, and oxygen and methane levels.

What to consider for your own project

  1. Specify the full gas range, including the leanest gas you expect in the future.
  2. Ask about the pilot. Lean gas needs a reliable ignition source.
  3. Check what is excluded. Here: installation, civil works, gas analysers, dewatering ahead of the plant, and condensate management.
  4. Plan for the hazardous area. The equipment was priced against the ESA industry codes of practice for DSEAR.
  5. Consider options. A standby blower, an acoustic enclosure or a cage can be added.

For comparison, see the UK LFTGN03 guidance on managing landfill gas.

FAQ

What is the lowest methane level a flare can burn?

This design is rated down to 12% methane, using a propane pilot and temperature control.

What does turndown mean?

The ratio of maximum to minimum thermal output. Here it is 5:1.

Why does the flare have a purge blower?

To clear combustible gas from the pipework and chamber before ignition.

Does the package include gas analysers?

No. Logging and control are included, but the analysers are supplied by others.

Sizing a flare for ageing landfill gas?

Send us your gas forecast and we will recommend a flare and blower.

Start your enquiry :


Translate »
organics.co.uk
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.