An elevated landfill gas flare specification should state the gas flow, the pressure head, the flame temperature range, the materials, the control philosophy and the site conditions, such as wind loading. This post uses a 600 scfm (roughly 1,000 m³/h) elevated flare package supplied to a US landfill to show what a complete specification looks like, and how a quotation and an order confirmation fit together.
The challenge: a compact flare for a landfill power site
A US landfill operator specified an elevated, pre-aerated flare to burn landfill gas. Elevated flares (the “candlestick” type) are compact and simpler than enclosed ground flares, and they suit sites where an enclosed, high-temperature flare is not required. The specification included a 100 mph wind-loading requirement and a control panel to be housed in the client’s own enclosure.
The approach: what the package contained
The blower
The blower was a direct-drive unit with an ExN (Zone 2) electric motor, delivering 600 scfm against a total head of about 60 inches water column (roughly 150 mbar). Its casing, pedestal and impeller were all stainless steel. That choice has a consequence: a stainless steel blower is classed as spark-proof, rather than merely spark-resistant, as is the case with carbon steel units.
Direct drive was chosen because it needs no belt changes. It also makes it easier to fit an acoustic enclosure later. Without one, noise is about 90 dB(A) at 3 feet. A belt-driven blower was offered as an option for sites where flow rates vary widely, and an acoustic enclosure was offered as another.
The flare
The flare stack has a 321 stainless steel tip and shroud, about 16 feet 5 inches (5 m) high. Flame temperature is adjusted manually up to 1,560°F (about 850°C), with automatic temperature control available as an option. The combustion range is 25% to 60% methane, with a design flame temperature of 1,500°F (about 815°C) when methane exceeds 25%. Turndown is 5:1.
Ignition without bottled fuel
Ignition is landfill-gas based, with a UV sensor and spark electrode, so the flare lights directly on the gas within the combustion shroud. This eliminates the need for LPG bottles. The flare was supplied with no pilot. The operator can select what happens if the flame is lost: continue running, shut down, or vent only.
Protection and instrumentation
A flame arrester with a stainless steel element sits on the blower outlet, with a pressure drop of about 4 inches water column at 600 scfm. A pressure switch on the outlet detects gas flow interruption. There is a gas sample point on the outlet, and an orifice plate flow meter with a digital readout of flow and total. A knit-mesh demister and filter protect the blower from liquid. Fasteners are 310 stainless steel at high temperature and 304 elsewhere, and the pipework is stainless steel on a hot-dip galvanised frame.
Electrics and controls
The blower motor is 15 hp (11 kW) on a 460 V, three-phase, 60 Hz supply, with a full-load current of about 21 amps and a start current of about 66 amps through a star-delta starter. The PLC is an Allen Bradley unit, and the control panel has low-pressure shutdown on the booster, a digital flow totaliser, a vent/burn interlock and manual override on all key functions. There is also a provision to monitor the level in an existing sump and run the existing pump, with hours-run recorded.
Why the details matter
Notice that the order confirmation repeats and extends the quotation. Some items were originally optional (such as the flow meter and digital readout) and became firm, while others were confirmed as not wanted (no pilot, no telemetry, no heated drain). That is how a specification should work: the quotation proposes, the order confirmation records what was agreed, and the drawings and electrical details close the gaps.
The quotation also claimed three advantages for this type of flare: low maintenance, because replacement parts are standard items; corrosion resistance, through stainless steel in the blower and knockout pot and galvanised steel elsewhere; and accurate combustion control to limit emissions.
What to consider for your own project
- State the units. Mixed units (scfm, inches water column, °F) are a common source of confusion. Convert and confirm.
- Specify the wind load and the standards for the foundation fixings.
- Decide on spark-proof or spark-resistant. Stainless steel casings give you the former.
- Choose the drive for your flow pattern. Direct drive suits stable flow. A belt-driven unit may suit wide variations.
- Check whether an elevated flare is acceptable for your regulator. In the UK, enclosed flares are expected to reach set temperatures and residence times. See the Environment Agency’s LFTGN05 and our comparison of ground and elevated flares.
FAQ
What is an elevated flare?
A flare that burns gas at the top of a stack, usually at a lower and less tightly controlled temperature than an enclosed ground flare.
Why does the blower material matter?
A fully stainless steel blower is spark-proof, which is a stronger classification than spark-resistant.
Do I need LPG for ignition?
Not necessarily. This flare ignites directly on landfill gas, so no LPG bottles were needed.
How loud is a direct-drive blower?
About 90 dB(A) at 3 feet without an acoustic enclosure.
Specifying an elevated flare?
Send us your flow, head and site conditions and we will draft a specification. Related reading: options worth adding to an elevated flare.